First published in Great Britain and the United States in 2006 by ISTE Ltd Apart from any fair dealing for the purposes of research or private study, or criticism or review, as permitted under the Copyright, Designs and Patents Act 1988, this publication may only be reproduced, stored or transmitted, in any form or by any means, with the prior permission in writing of the publishers, or in the case of reprographic reproduction in accordance with the terms and licenses issued by the CLA. Enquiries concerning reproduction outside these terms should be sent to the publishers at the undermentioned address: ISTE Ltd 6 Fitzroy Square London W1T 5DX UK
ISTE USA 4308 Patrice Road Newport Beach, CA 92663 USA
www.iste.co.uk © ISTE Ltd, 2006 The rights of Christophe Prévé to be identified as the author of this work have been asserted by him in accordance with the Copyright, Designs and Patents Act 1988. Library of Congress Cataloging-in-Publication Data Prévé, Christophe, 1964Protection of electrical networks / Christophe Prévé. p. cm. Includes index. ISBN-13: 978-1-905209-06-4 ISBN-10: 1-905209-06-1 1. Electric networks--Protection. I. Title. TK454.2.P76 2006 621.319'2--dc22 2006008664 British Library Cataloguing-in-Publication Data A CIP record for this book is available from the British Library ISBN 10: 1-905209-06-1 ISBN 13: 978-1-905209-06-4 Printed and bound in Great Britain by Antony Rowe Ltd, Chippenham, Wiltshire.
Table of Contents
Chapter 1. Network Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1. General structure of the private distribution network . . . . . . . . . . . . 1.2. The supply source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3. HV consumer substations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4. MV power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.1. Different MV service connections . . . . . . . . . . . . . . . . . . . . . 1.4.2. MV consumer substations . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5. MV networks inside the site . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5.1. MV switchboard power supply modes . . . . . . . . . . . . . . . . . . 1.5.2. MV network structures. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.6. LV networks inside the site . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.6.1. LV switchboard supply modes . . . . . . . . . . . . . . . . . . . . . . . 1.6.2. LV switchboards backed up by generators . . . . . . . . . . . . . . . . 1.6.3. LV switchboards backed up by an uninterruptible power supply (UPS) . 1.7. Industrial networks with internal generation . . . . . . . . . . . . . . . . . 1.8. Examples of standard networks . . . . . . . . . . . . . . . . . . . . . . . . .
11 13 13 13 16 16 19 19 19 25 31 31 35 36 42 44
Chapter 2. Earthing Systems . . . . . . . . . . . . . . . . . . . . . . . . 2.1. Earthing systems at low voltage. . . . . . . . . . . . . . . . . . . 2.1.1. Different earthing systems – definition and arrangements . 2.1.2. Comparison of different earthing systems in low voltage . 2.1.2.1. Unearthed or impedance-earthed neutral (IT system). . 2.1.2.2. Directly earthed neutral (TT system) . . . . . . . . . . . 2.1.2.3. Connecting the exposed conductive parts to the neutral (TNC – TNS systems) . . . . . . . . . . . . . . . . . . . . . . . . . 2.2. Medium voltage earthing systems . . . . . . . . . . . . . . . . . 2.2.1. Different earthing systems – definition and arrangements . 2.2.2. Comparison of different medium voltage earthing systems 2.2.2.1. Direct earthing . . . . . . . . . . . . . . . . . . . . . . . . 2.2.2.2. Unearthed . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2.2.3. Limiting resistance earthing. . . . . . . . . . . . . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
53 54 55 58 58 59
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
60 61 61 63 63 63 64
6
Protection of Electrical Networks
2.2.2.4. Limiting reactance earthing . . . . . . . . . . . . . . . . . . . . . 2.2.2.5. Peterson coil earthing . . . . . . . . . . . . . . . . . . . . . . . . 2.3. Creating neutral earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.1. MV installation resistance earthing . . . . . . . . . . . . . . . . . . 2.3.2. Reactance or Petersen coil earthing of an MV installation. . . . . 2.3.3. Direct earthing of an MV or LV installation . . . . . . . . . . . . . 2.4. Specific installation characteristics in LV unearthed systems . . . . . 2.4.1. Installing a permanent insulation monitor . . . . . . . . . . . . . . 2.4.2. Installing an overvoltage limiter . . . . . . . . . . . . . . . . . . . . 2.4.3. Location of earth faults by a low frequency generator (2–10 Hz) 2.5. Specific installation characteristics of an MV unearthed system . . . 2.5.1. Insulation monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5.2. Location of the first insulation fault . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
64 65 66 66 70 70 70 71 71 71 73 73 75
. . . . . .
. . . . . .
77 77 77 78 79 80
Chapter 4. Short-circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1. Establishment of short-circuit currents and wave form . . . . . . . . . . 4.1.1. Establishment of the short-circuit at the utility’s supply terminals . 4.1.2. Establishment of the short-circuit current at the terminals of a generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2. Short-circuit current calculating method. . . . . . . . . . . . . . . . . . . 4.2.1. Symmetrical three-phase short-circuit. . . . . . . . . . . . . . . . . . 4.2.1.1. Equivalent impedance of an element across a transformer. . . . 4.2.1.2. Impedance of parallel links . . . . . . . . . . . . . . . . . . . . . . 4.2.1.3. Expression of impedances as a percentage and short-circuit voltage as a percentage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2.1.4. Impedance values of different network elements . . . . . . . . . 4.2.1.5. Contribution of motors to the short-circuit current value . . . . 4.2.1.6. Example of a symmetrical three-phase short-circuit calculation 4.2.2. Solid phase-to-earth short-circuit (zero fault impedance) . . . . . 4.2.2.1. positive, negative and zero-sequence impedance values of different network elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2.3. The phase-to-phase short-circuit clear of earth . . . . . . . . . . . . 4.2.4. The two-phase-to-earth short-circuit. . . . . . . . . . . . . . . . . . . 4.3. Circulation of phase-to-earth fault currents . . . . . . . . . . . . . . . . . 4.3.1. Unearthed or highly impedant neutral . . . . . . . . . . . . . . . . . . 4.3.2. Impedance-earthed neutral (resistance or reactance) . . . . . . . . . 4.3.3. Tuned reactance or Petersen coil earthing . . . . . . . . . . . . . . . 4.3.4. Directly earthed neutral . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .
81 82 83
. . . . .
87 92 93 94 95
Chapter 3. Main Faults Occurring in Networks and Machines . 3.1. Short-circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.1. Short-circuit characteristics . . . . . . . . . . . . . . . . . 3.1.2. Different types of short-circuits . . . . . . . . . . . . . . 3.1.3. Causes of short-circuits . . . . . . . . . . . . . . . . . . . 3.2. Other types of faults. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. 96 . 98 . 106 . 107 . 114 . . . . . . . .
117 125 125 126 129 130 131 132
Table of Contents
4.3.5. Spreading of the capacitive current in a network with several outgoing feeders upon occurrence of an earth fault. . . . . . . . . . . . . . 4.4. Calculation and importance of the minimum short-circuit current . . . 4.4.1. Calculating the minimum short-circuit current in low voltage in relation to the earthing system . . . . . . . . . . . . . . . . . . . . . . . . 4.4.1.1. Calculating the minimum short-circuit current in a TN system . 4.4.1.2. Calculating the minimum short-circuit current in an IT system without a distributed neutral . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.1.3. Calculating the minimum short-circuit in an IT system with distributed neutral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.1.4. Calculating the minimum short-circuit in a TT system . . . . . . 4.4.1.5. Influence of the minimum short-circuit current on the choice of circuit-breakers or fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.2. Calculating the minimum short-circuit current for medium and high voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.3. Importance of the minimum short-circuit calculation for protection selectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 5. Consequences of Short-circuits . . . 5.1. Thermal effect . . . . . . . . . . . . . . . . . 5.2. Electrodynamic effect. . . . . . . . . . . . . 5.3. Voltage drops. . . . . . . . . . . . . . . . . . 5.4. Transient overvoltages . . . . . . . . . . . . 5.5. Touch voltages . . . . . . . . . . . . . . . . . 5.6. Switching surges. . . . . . . . . . . . . . . . 5.7. Induced voltage in remote control circuits.
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
7
. 133 . 137 . 138 . 139 . 144 . 150 . 151 . 156 . 160 . 162 . . . . . . . .
163 163 165 167 168 169 169 170
Chapter 6. Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . 6.1. Current transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.1. Theoretical reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.2. Saturation of the magnetic circuit . . . . . . . . . . . . . . . . . . . . . 6.1.3. Using CTs in electrical networks. . . . . . . . . . . . . . . . . . . . . . 6.1.3.1. General application rule . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.3.2. Composition of a current transformer . . . . . . . . . . . . . . . . . 6.1.3.3. Specifications and definitions of current transformer parameters. 6.1.3.4. Current transformers used for measuring in compliance with standard IEC 60044-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.3.5. Current transformers used for protection in compliance with standard IEC 60044-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.3.6. Current transformers used for protection in compliance with BS 3938 (class X) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.3.7. Correspondence between IEC 60044-1 and BS 3938 CT specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.3.8. Use of CTs outside their nominal values . . . . . . . . . . . . . . . 6.1.3.9. Example of a current transformer rating plate . . . . . . . . . . . . 6.1.4. Non-magnetic current sensors . . . . . . . . . . . . . . . . . . . . . . .
173 173 173 176 181 181 182 183 185 187 188 189 192 197 197
8
Protection of Electrical Networks
6.2. Voltage transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.1. General application rule . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.2. Specifications and definitions of voltage transformer parameters 6.2.3. Voltage transformers used for measuring in compliance with IEC 60044-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.4. Voltage transformers used for protection in compliance with IEC 60044-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.5. Example of the rating plate of a voltage transformer used for measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 198 . . 198 . . 199 . . 202 . . 203 . . 205
Chapter 7. Protection Functions and their Applications . . . . . . . . . . . . . 7.1. Phase overcurrent protection (ANSI code 50 or 51) . . . . . . . . . . . . . 7.2. Earth fault protection (ANSI code 50 N or 51 N, 50 G or 51 G). . . . . . 7.3. Directional overcurrent protection (ANSI code 67) . . . . . . . . . . . . . 7.3.1. Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4. Directional earth fault protection (ANSI code 67 N) . . . . . . . . . . . . 7.4.1. Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4.2. Study and setting of parameters for a network with limiting resistance earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4.3. Study and setting of parameters for an unearthed network. . . . . . . 7.5. Directional earth fault protection for compensated neutral networks (ANSI code 67 N). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6. Differential protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6.1. High impedance differential protection . . . . . . . . . . . . . . . . . . 7.6.1.1. Operation and dimensioning of elements . . . . . . . . . . . . . . 7.6.1.2. Application of high impedance differential protection . . . . . . . 7.6.1.3. Note about the application of high impedance differential protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6.2. Pilot wire differential protection for cables or lines (ANSI code 87 L) 7.6.3. Transformer differential protection (ANSI code 87 T) . . . . . . . . . 7.7. Thermal overload protection (ANSI code 49). . . . . . . . . . . . . . . . . 7.8. Negative phase unbalance protection (ANSI code 46) . . . . . . . . . . . 7.9. Excessive start-up time and locked rotor protection (ANSI code 51 LR) 7.10. Protection against too many successive start-ups (ANSI code 66). . . . 7.11. Phase undercurrent protection (ANSI code 37) . . . . . . . . . . . . . . . 7.12. Undervoltage protection (ANSI code 27) . . . . . . . . . . . . . . . . . . 7.13. Remanent undervoltage protection (ANSI code 27) . . . . . . . . . . . . 7.14. Positive sequence undervoltage and phase rotation direction protection (ANSI code 27 d – 47) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.15. Overvoltage protection (ANSI code 59) . . . . . . . . . . . . . . . . . . . 7.16. Residual overvoltage protection (ANSI code 59 N) . . . . . . . . . . . . 7.17. Under or overfrequency protection (ANSI code 81) . . . . . . . . . . . . 7.18. Protection against reversals in reactive power (ANSI code 32 Q) . . . . 7.19. Protection against reversals in active power (ANSI code 32 P) . . . . . 7.20. Tank earth leakage protection (ANSI code 50 or 51) . . . . . . . . . . .
207 208 210 214 217 224 226 228 234 238 243 244 246 256 265 265 276 279 288 292 294 295 297 298 298 300 301 302 303 304 306
Table of Contents
7.21. Protection against neutral earthing impedance overloads (ANSI code 50 N or 51 N) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.22. Overall network earth fault protection by monitoring the current flowing through the earthing connection (ANSI code 50 N or 51 N, 50 G or 51 G) . . . 7.23. Protection using temperature monitoring (ANSI code 38 – 49 T) . . . . 7.24. Voltage restrained overcurrent protection (ANSI code 50 V or 51 V) . 7.25. Protection by gas, pressure and temperature detection (DGPT) . . . . . 7.26. Neutral to neutral unbalance protection (ANSI code 50 N or 51 N) . . .
9
307 308 309 311 314 315
Chapter 8. Overcurrent Switching Devices . . . . . . . . . . . . . . 8.1. Low voltage circuit-breakers . . . . . . . . . . . . . . . . . . . 8.2. MV circuit-breakers (according to standard IEC 62271-100) 8.3. Low voltage fuses . . . . . . . . . . . . . . . . . . . . . . . . . . 8.3.1. Fusing zones – conventional currents . . . . . . . . . . . . 8.3.2. Breaking capacity. . . . . . . . . . . . . . . . . . . . . . . . 8.4. MV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
317 317 325 331 331 334 334
Chapter 9. Different Selectivity Systems . . . . . . . 9.1. Amperemetric selectivity. . . . . . . . . . . . . 9.2. Time-graded selectivity. . . . . . . . . . . . . . 9.3. Logic selectivity . . . . . . . . . . . . . . . . . . 9.4. Directional selectivity. . . . . . . . . . . . . . . 9.5. Selectivity by differential protection . . . . . . 9.6. Selectivity between fuses and circuit-breakers
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
341 341 345 349 354 355 356
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
Chapter 10. Protection of Network Elements . . . . . . . . . . . . . . . . 10.1. Network protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.1. Earth fault requirements for networks earthed via a limiting resistance (directly or by using an artificial neutral) . . . . . . . . . . 10.1.2. Earth fault requirement for unearthed networks . . . . . . . . 10.1.3. Requirements for phase-to-phase faults . . . . . . . . . . . . . 10.1.4. Network with one incoming feeder. . . . . . . . . . . . . . . . 10.1.4.1. Protection against phase-to-phase faults. . . . . . . . . . . 10.1.4.2. Protection against earth faults . . . . . . . . . . . . . . . . . 10.1.5. Network with two parallel incoming feeders . . . . . . . . . . 10.1.5.1. Protection against phase-to-phase faults. . . . . . . . . . . 10.1.5.2. Protection against earth faults . . . . . . . . . . . . . . . . . 10.1.6. Network with two looped incoming feeders . . . . . . . . . . 10.1.6.1. Protection against phase-to-phase faults. . . . . . . . . . . 10.1.6.2. Protection against earth faults . . . . . . . . . . . . . . . . . 10.1.7. Loop network . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.7.1. Protection at the head of the loop. . . . . . . . . . . . . . . 10.1.8. Protection by section . . . . . . . . . . . . . . . . . . . . . . . . 10.2. Busbar protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.1. Protection of a busbar using logic selectivity . . . . . . . . . .
. . . . 361 . . . . 361 . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
362 369 371 372 373 375 381 381 384 390 390 393 399 399 401 412 412
10
Protection of Electrical Networks
10.2.2. Protection of a busbar using a high impedance differential protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3. Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3.1. Transformer energizing inrush current. . . . . . . . . . . . . . . . . . 10.3.2. Value of the short-circuit current detected by the HV side protection during a short-circuit on the LV side for a delta-star transformer . . . . . . . . 10.3.3. Faults in transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3.4. Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3.4.1. Specific protection against overloads . . . . . . . . . . . . . . . . 10.3.4.2. Specific protection against internal phase short-circuits . . . . . 10.3.4.3. Specific protection against earth faults . . . . . . . . . . . . . . . 10.3.4.4. Switch-fuse protection . . . . . . . . . . . . . . . . . . . . . . . . . 10.3.4.5. Circuit-breaker protection . . . . . . . . . . . . . . . . . . . . . . . 10.3.5. Examples of transformer protection . . . . . . . . . . . . . . . . . . . 10.3.6. Transformer protection setting indications . . . . . . . . . . . . . . . 10.4. Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.4.1. Protection of medium voltage motors . . . . . . . . . . . . . . . . . . 10.4.1.1. Examples of motor protection. . . . . . . . . . . . . . . . . . . . . 10.4.1.2. Motor protection setting indications . . . . . . . . . . . . . . . . . 10.4.2. Protection of low voltage asynchronous motors . . . . . . . . . . . . 10.5. AC generator protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5.1. Examples of generator protection devices. . . . . . . . . . . . . . . . 10.5.2. Generator protection setting indications . . . . . . . . . . . . . . . . . 10.6. Capacitor bank protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.6.1. Electrical phenomena related to energization. . . . . . . . . . . . . . 10.6.2. Protection of Schneider low voltage capacitor banks . . . . . . . . . 10.6.3. Protection of Schneider medium voltage capacitor banks . . . . . . 10.8. Protection of direct current installations . . . . . . . . . . . . . . . . . . . 10.8.1. Short-circuit current calculation . . . . . . . . . . . . . . . . . . . . . 10.8.2. Characteristics of insulation faults and switchgear . . . . . . . . . . 10.8.3. Protection of persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.9. Protection of uninterruptible power supplies (UPS) . . . . . . . . . . . . 10.9.1. Choice of circuit-breaker ratings . . . . . . . . . . . . . . . . . . . . . 10.9.2. Choice of circuit-breaker breaking capacity . . . . . . . . . . . . . . 10.9.3. Selectivity requirements . . . . . . . . . . . . . . . . . . . . . . . . . .
413 414 414 417 423 424 424 424 424 425 432 436 438 439 440 446 448 451 452 457 460 462 463 469 470 479 479 482 483 483 484 485 485
Appendix A. Transient Current Calculation of Short-circuit Fed by Utility Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487 Appendix B. Calculation of Inrush Current During Capacitor Bank Energization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493 Appendix C. Voltage Peak Value and Current r m.s Value, at the Secondary of a Saturated Current Transformer . . . . . . . . . . . . . . 501 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
Chapter 1
Network Structures
Definition Standard IEC 60038 defines voltage ratings as follows: – Low voltage (LV): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V - 690 V - 1,000 V (at 50 Hz). – Medium voltage (MV): for a phase-to-phase voltage between 1,000 V and 35 kV, the standard ratings are: 3.3 kV - 6.6 kV - 11 kV - 22 kV - 33 kV. – High voltage (HV): for a phase-to-phase voltage between 35 kV and 230 kV, the standard ratings are: 45 kV - 66 kV - 110 kV - 132 kV - 150 kV - 220 kV. In this chapter we will look at: – types of HV and MV consumer substations; – structure of MV networks inside a site; – structure of LV networks inside a site; – structure of systems with a back-up power supply. Six standard examples of industrial network structures are given at the end of the chapter. Each structure is commented upon and divided up so that each functional aspect can be considered. (NC) means that the switch or circuit-breaker is closed in normal conditions. (NO) means that the switch or circuit-breaker is open in normal conditions.
Network Structures
13
1.1. General structure of the private distribution network Generally, with an HV power supply, a private distribution network comprises (see Figure 1-1): – an HV consumer substation fed by one or more sources and made up of one or more busbars and circuit-breakers; – an internal generation source; – one or more HV/MV transformers; – a main MV switchboard made up of one or more busbars; – an internal MV network feeding secondary switchboards or MV/LV substations; – MV loads; – MV/LV transformers; – low voltage switchboards and networks; – low voltage loads.
1.2. The supply source The power supply of industrial networks can be LV, MV or HV. The voltage rating of the supply source depends on the consumer supply power. The greater the power required, the higher the voltage must be.
1.3. HV consumer substations The most usual supply arrangements adopted in HV consumer substations are: Single power supply (see Figure 1-2) Advantage: – reduced cost. Disadvantage: – low reliability. Note: the isolators associated with the HV circuit-breakers have not been shown.
Network Structures
15
Operating mode: – normal: - Both incoming circuit-breakers are closed, as well as the coupler isolator. - The transformers are thus simultaneously fed by two sources. – disturbed: - If one source is lost, the other provides the total power supply. Advantages: – Very reliable in that each source has a total network capacity. – Maintenance of the busbar possible while it is still partially operating. Disadvantages: – More costly solution. – Only allows partial operation of the busbar if maintenance is being carried out on it. Note: the isolators associated with the HV circuit-breakers have not been shown. Dual fed double bus system (see Figure 1-4) Operating mode: – normal: - Source 1 feeds busbar BB1 and feeders Out1 and Out2. - Source 2 feeds busbar BB2 and feeders Out3 and Out4. - The bus coupler circuit-breaker can be kept closed or open. – disturbed: - If one source is lost, the other provides the total power supply. - If a fault occurs on a busbar (or maintenance is carried out on it), the bus coupler circuit-breaker is tripped and the other busbar feeds all the outgoing lines. Advantages: – Reliable power supply. – Highly flexible use for the attribution of sources and loads and for busbar maintenance. – Busbar transfer possible without interruption. Disadvantage: – More costly in relation to the single busbar system. Note: the isolators associated with the HV circuit-breakers have not been shown.
38
Protection of Electrical Networks
Device name
Ref. no
Function
Rectifiercharger
(1)
Transforms the alternating voltage of a supply network into a direct voltage which will: – feed the inverter; – continually provide the charge for the storage battery.
Storage battery
(2)
Provides a back-up supply to feed the inverter in case: – the supply network disappears (power cut); – the supply network is disturbed (disturbances leading to insufficient quality).
Inverter
(3)
Transforms the direct voltage from the rectifier-charger or storage battery into three-phase alternating voltage with more severe tolerances than those of the network (supplies an alternating current close to the theoretical sine curve).
Static contactor
(4)
Switches over the load supply from the inverter to network 2 (standby) without interruption (no cut due to mechanical switching device changeover time – the switchover is carried out using electronic components in a time < 1 ms). This switchover is performed if the inverter stops working for one of the following reasons: – switched off; – overload beyond the limiting capacities of the inverter; – internal anomaly.
Manual by-pass
(5)
Manual switch which allows the user to be fed by network 2 (standby), while maintenance is being carried out. Its presence is indispensable when the network frequencies upstream and downstream of the UPS are identical.
Insulating transformer
(6)
Provides upstream and downstream insulation when the supply is via network 2. It is especially used when the upstream and downstream earthing systems are different.
Manual switches Battery circuitbreakers
(7) (8)
Provides insulation of the different parts when maintenance is being carried out.
(9) (10)
Table 1-1: function of different devices making up a UPS system
Network Structures
45
Example 2 (see Figure 1-36) Network structure: – MV consumer substation; – the main MV switchboard can be backed up by a generator set and feeds three transformers; – the main low voltage switchboards MLVS1, MLVS2 and MLVS3 are independent and each one has an outgoing feeder to an uninterruptible power supply feeding a priority circuit; – the low voltage network is of the arborescent radial type, and the motor control centers and terminal boxes are fed by a single source. Example 3 (see Figure 1-37) Network structure: – MV consumer substation; – the main MV switchboard can be backed up by a generator set and it feeds two MV/LV transformers; – the main low voltage switchboard has a dual power supply with coupler; – each bus section of the main low voltage switchboard has a UPS system feeding a priority circuit; – the secondary switchboards, terminal boxes and motor control centers are fed by a single source. Example 4 (see Figure 1-38) Network structure: – MV consumer substation; – the main MV switchboard can be backed up by a generator set. It feeds two MV/LV transformers in a single line supply system, four MV secondary switchboards in a loop system, and a secondary MV switchboard in a single line supply system; – the low voltage network is of the arborescent radial type.
Network Structures
49
Example 5 (see Figure 1-39) Network structure: – MV consumer substation; – two MV ratings: 20 kV and 6 kV; – the main MV switchboard fed at 20 kV can be backed up by a set of four generators. It feeds: - an MV 20 kV network in a loop system comprising three secondary switchboards MV4, MV5 and MV6; - two 20 kV/6kV transformers in a single line supply system; – the MV main switchboard is made up two bus sections fed at 6 kV by two sources with coupler; – it feeds three MV secondary switchboards and two 6 kV/LV transformers in a single line supply system; – the secondary switchboard MV2 is fed by two sources with coupler and is made up of two bus sections. It feeds two 6 kV motors and two 6 kV/LV transformers in a single line supply system; – the secondary switchboards MV1 and MV3 are fed by a single source. Each feeds a 6 kV/LV transformer and a 6 kV motor; – the main low voltage switchboard MLVS1 can be backed up by a generator; – the main low voltage switchboard MLVS2 is fed by two sources with coupler; – the main low voltage switchboard MLVS3 is fed by a single source; – the motor control centers 1 and 3 are fed by a single source; – the motor control center 2 is fed by 2 sources with no coupler. Example 6 (see Figure 1-40) Network structure: – HV consumer substation fed at 90 kV by two HV sources with no coupler (isolators ISO1 and ISO2 cannot operate when loaded and are in closed position during normal operation); – the central HV/MV transformer is used as back-up. The transformers can be connected on the MV side via the circuit-breakers (moreover, the on-load tap changers allow the currents supplied by each transformer to be balanced); – the network has two MV ratings: 20 kV and 6 kV; – the main MV switchboard is fed at 20 kV by three sources with coupler. It is made up of three bus sections; – the secondary switchboards MV1, MV2 and MV3 are fed at 6 kV by two sources (transformers) with coupler coming from two different busbars;
54
Protection of Electrical Networks
The neutral may be directly connected to earth or connected through a resistor or a reactor. In the first case, we say that the neutral is directly earthed and in the second case we say that it is impedance-earthed. When a connection has not been made between the neutral point and earth, we say that the neutral is unearthed. In a network, the earthing system plays a very important role. When an insulation fault occurs or a phase is accidentally earthed, the values taken by the fault currents, the touch voltages and overvoltages are closely linked to the type of neutral earthing connection. A directly earthed neutral strongly limits overvoltages but it causes very high fault currents, whereas an unearthed neutral limits fault currents to very low values but encourages the occurrence of high overvoltages. In any installation, service continuity in the event of an insulation fault is also directly related to the earthing system. An unearthed neutral permits service continuity during an insulation fault. Contrary to this, a directly earthed neutral, or low impedance-earthed neutral, causes tripping as soon as the first insulation fault occurs. The extent of the damage to some equipment, such as motors and generators presenting an internal insulation fault, also depends on the earthing system. In an earthed network, a machine affected by an insulation fault suffers extensive damage due to the large fault currents. However, in an unearthed or high impedance-earthed network, the damage is reduced, but the equipment must have an insulation level compatible with the level of overvoltages able to cope in this type of network. The choice of earthing system in both low voltage and medium voltage networks depends on the type of installation as well as the type of network. It is also influenced by the type of loads and service continuity required. 2.1. Earthing systems at low voltage We shall first of all define the different low voltage earthing systems and then compare the advantages and disadvantages of each one.
Earthing Systems
59
Disadvantages: – Requires maintenance personnel to monitor the system during use. – Requires a good level of network insulation (which means that the network must be broken up if widespread, and that loads with high leakage current must be supplied by insulating transformers). – Tripping checks for two simultaneous faults should be carried out if possible when the network is being designed using calculation, and must be performed during commissioning using measurement. – Overvoltage limiters must be installed. – Requires all the installation’s exposed conductive parts to be equipotentially bonded; if this is not possible RCDs must be installed. – Avoid distributing the neutral conductor. In the IT system, it is in fact recommended not to distribute the neutral for the following reasons: - if the neutral conductor is distributed, a fault affecting it will eliminate the advantages attached to the IT system; - if the neutral is distributed, it must be protected (except for specific cases); - the fact of not distributing the neutral facilitates the choice of overcurrent protective devices (see section 4.4.1.3) and fault location. – Locating faults is difficult in widespread networks. – When an insulation fault in relation to the earth occurs, the voltage of the two unaffected phases in relation to the earth takes on the value of the phase-to-phase voltage (see section 7.16). Equipment must therefore be selected with this in mind. 2.1.2.2. Directly earthed neutral (TT system) Operating technique: – Switching upon occurrence of the first insulation fault. Technique for protecting persons: – Earthing of exposed conductive parts combined with the compulsory use of RCDs (at least one at the head of the installation). – All exposed conductive parts protected by the same RCD must be connected to the same earth. – Simultaneously accessible exposed conductive parts must be connected to the same earth. Advantages: – The simplest system to design, implement, monitor and use.
60
Protection of Electrical Networks
– Does not require permanent monitoring during use (only a periodic inspection test of the RCDs may be necessary). – Moreover, the presence of RCDs prevents the risk of fire when their sensitivity is below or equal to 500 mA (see standard IEC 60364-4, section 482.2.10). – Easy location of faults. – Upon occurrence of an insulation fault, the short-circuit current is small. Disadvantages: – Switching upon occurrence of the first insulation fault. – Use of an RCD on each outgoing feeder to obtain total selectivity. – Special measures must be taken for the loads or parts of the installation causing high leakage currents during normal operation in order to avoid spurious tripping (feed the loads by insulating transformers or use high threshold RCDs, compatible with the exposed conductive part earth resistance). 2.1.2.3. Connecting the exposed conductive parts to the neutral (TNC – TNS systems) Operating technique: – Switching upon occurrence of the first insulation fault. Technique for protecting persons: – Imperative interconnection and earthing of exposed conductive parts. – Switching on occurrence of the first fault via an overcurrent protective device (circuit-breaker or fuse). Advantages: – The TNC system may be less costly upon installation (elimination of one switchgear pole and one conductor). – Use of overcurrent protective devices to ensure protection against indirect contact. Disadvantages: – Switching on occurrence of the first insulation fault. – The TNC system involves the use of fixed and rigid trunkings (see section 413.1.3.2 of standard IEC 60364-4). – Requires earthing connections to be evenly placed in the installation so that the protective conductor remains at the same potential as the earth. – A tripping check on occurrence of the insulation fault should be carried out, if possible, when the network is being designed using calculations, and must be performed during commissioning using measurements; this check is the only
Earthing Systems
63
2.2.2. Comparison of different medium voltage earthing systems The various earthing systems in medium voltage systems are different in the way they operate and each has its advantages and disadvantages, which we shall now consider. 2.2.2.1. Direct earthing (see Table 2-1(a)) Operating technique: – Compulsory switching on occurrence of the first insulation fault. Advantages: – Reduces the risk of overvoltages occurring. – Authorizes the use of equipment with a normal phase to earth insulating level. Disadvantages: – Compulsory tripping upon occurrence of the first fault. – Very high fault currents leading to maximum damage and disturbance (creation of induced currents in telecommunication networks (see section 5.7) and auxiliary circuits). – The risk for personnel is high while the fault lasts; the touch voltages which develop being high. – Requires the use of differential protection devices (see section 7.6) so that the fault clearance time is not long. These systems are costly. 2.2.2.2. Unearthed (see Table 2-1(b)) Operating technique: – No switching on occurrence of the first insulation fault – it is thus compulsory: - to carry out permanent insulation monitoring; - to indicate the first insulation fault; - to locate and clear the first insulation fault; - to switch upon occurrence of the second insulation fault (double fault). Advantages: – Provides continuity of service by only tripping upon occurrence of the second fault, subject to the network capacity not leading to a high earth fault current that would be dangerous for personnel and loads on occurrence of the first fault.
64
Protection of Electrical Networks
Disadvantages: – The unearthed neutral involves: - the use of equipment whose phase-to-earth insulation level is at least equal to that of the phase-to-phase level; indeed, when a permanent phase-earth fault occurs, the voltage of both unaffected phases in relation to earth takes on the value of the phase-to-phase voltage if tripping is not triggered on occurrence of the first fault (see section 7.16); cables, rotating machines, transformers and loads must therefore be chosen with this in mind; - the risk of high internal overvoltages making it advisable to reinforce the equipment insulation; - the compulsory insulation monitoring, with visual and audible indication of the first fault if tripping is not triggered until the second fault occurs; - the presence of maintenance personnel to monitor and locate the first fault during use; - some difficulties implementing selective protection devices upon occurrence of the first fault (see section 7.4.3, directional earth fault protection); - the risk of ferro-resonance. 2.2.2.3. Limiting resistance earthing (see Table 2-1(c)) Operating technique: – Switching upon occurrence of the first fault. Advantages: – Limits fault currents (reduced damage and disturbance). – Dampens overvoltages of internal origin in that the limiting current I A is twice as high as the capacitive current I C giving I A > 2 I C . – Does not require the use of equipment, and in particular cables, having a special phase/earth insulation level. – Allows the use of simple selective protection devices. Disadvantages: – Tripping on the first fault. 2.2.2.4. Limiting reactance earthing (see Table 2-1(d)) Operating technique: – Switching upon occurrence of the first insulation fault.
Earthing Systems
65
Advantages: – Limits the fault currents (reduced damage and disturbance). – Allows the implementation of simple selective protection devices if I L >> I C . – The coil, being of low resistance, does not have to dissipate a high heat load. Disadvantages: – May cause high overvoltages during earth fault clearance. – Compulsory tripping upon occurrence of the first fault. 2.2.2.5. Petersen coil earthing (see Table 2-1(e)) Operating technique: – No switching upon occurrence of the first fault. Advantages: – If the reactance is such that 3 L0 C0 ω2 = 1 is respected, the phase-earth fault current is zero: - spontaneous clearance of non-permanent earth faults; - the installation continues to operate in spite of there being a permanent fault, with tripping necessarily occurring on the second fault; - the first fault is indicated by the detection of the current flowing through the coil. The coil is dimensioned so that permanent operation is possible. Disadvantages: – Difficulties establishing the condition 3 L0 C0 ω2 = 1 due to uncertain knowledge of the network’s capacity: the result is that throughout the duration of the fault, a residual current circulates in the fault. Care must be taken to make sure this current is not dangerous for personnel and equipment. – The risk of overvoltages occurring is high. – Requires the presence of monitoring personnel. – Impossible to provide selective protection upon occurrence of the first fault if the coil has been tuned to 3 L0 C0 ω2 = 1 ; if it is systematically out of tune
(3 L0 C0 ω2 ≠ 1) selective protection upon occurrence of the first fault is complex
and costly (see section 7.5, directional earth fault protection for compensated neutral systems). – Risk of ferro-resonance.
68
Protection of Electrical Networks
Problem of resistance earthing when several transformers operate in parallel on one busbar Case 1: Each transformer has a non-disconnectable earthing resistor. The earth fault current varies according to the number of transformers in service (see Figure 2-8a), which may pose difficulties for the motors or for setting the threshold of earth fault protection devices. Moreover, directional earth fault protection devices must be used (see section 7.4) to locate faults coming from connections linking the transformers to the busbars (see section 10.1.5.2).
Figure 2-8a: direct earthing of each neutral point
Case 2: Each transformer has a disconnectable earthing resistor. A switching device makes it possible to have a single earthed neutral point whatever the number of transformers in service (see Figure 2-8b). The protective system is complex since it uses logical selectivity, taking into account the position of the switching devices and the state of the different earth fault protection devices. This system is used very little.
R
R L
R L
L
L: control logic taking into account the network configuration Figure 2-8b: earthing of each neutral point using a switching device
Earthing Systems
75
If there are other star-connected voltage transformers in the same network, the following must be installed: – a capacitor between the neutral of the voltage transformers and earth so that the monitor does not deliver a direct current via the voltage transformers (if this was the case, it would continually detect a fault). The advisable value of the capacitor is 2.5 µF with an insulation voltage of 1,600 V. – an overvoltage limiter allowing overvoltages to be run off to earth. When two networks with an insulation monitor can be coupled, a logic must be made so that the two monitors cannot operate in parallel because, if they did, one would deliver current into the other and they would continually detect a fault. 2.5.2. Location of the first insulation fault This can be done in one of two of the following ways: – by an efficient selectivity system (see sections 10.1.4.2, 10.1.5.2 and 10.1.6.2); – by successive tripping of each feeder until the fault is cleared. The latter method is not recommended as it leads to switching on the healthy feeders and overvoltages able to generate a double fault.
Chapter 3
Main Faults Occurring in Networks and Machines
3.1. Short-circuits 3.1.1. Short-circuit characteristics Short-circuits can be defined according to three main characteristics: – Their origin: - they may be mechanical: breakdown of conductors or accidental electrical connection between two conductors via a foreign body such as a tool or animal; - they may be electrical: following the degradation of the insulation between phases, or between phase and frame or earth, or resulting from internal overvoltages (switching surges) or atmospheric overvoltages (stroke of lightning); - they may be due to an operating error: earthing of a phase, connection between two different voltage supplies or different phases or closing of a switching device by mistake. – Their location: - the short-circuit may be generated inside equipment (cable, motor, transformer, switchboard, etc.), and it generally leads to deterioration; - the short-circuit may be generated outside equipment (cable, motor, transformer, switchboard, etc.). The consequences are limited to disturbances which may, in the course of time, lead to deterioration of the equipment in question and thereby cause an internal fault.
80
Protection of Electrical Networks
– Accidental reduction in electrical insulation (presence of animals, tree branches, tools left by carelessness on a busbar, etc.). – Destruction due to external causes (hit by a shovel, etc.). – Overvoltages causing a breakdown in equipment insulation (switching surges or lightning strike). 3.2. Other types of faults – On motors: - too many successive start-ups leading to overheating and mechanical shocks on couplings; - excessive start-up time or rotor locking leading to the same result; – On generators: - loss of excitation due to a fault in the rotor circuit (cut, short-circuit, etc.), leading to overheating of the rotor and stator and loss of synchronism with the network; - variations in frequency due to an overload or faulty operation of a frequency regulator (for a generator operating cut-off from the utility network). – Phase opposition connection of a generator with the network or of two parts of a network coming from different sources. – Overvoltages due to a lightning strike. – Switching surges (of a switch or circuit-breaker). – Overloads on cables, transformers, motors or generators. – Reversal of the direction of energy flow in the absence of an electrical fault. In the event of a power cut or a drop in voltage caused by the utility, an internal generation plant may supply energy to the utility. – Variations in voltage due to faulty operation of the on-load tap changers of a transformer, or network under or overload. – The presence of a negative-phase component due to a non-symmetrical voltage source, a large single-phase consumer, a connection error or phase cutting leads to overheating of the motors or generators, and a loss in generator synchronism.
Chapter 4
Short-circuits
All electrical installations must be protected against short-circuits every time there is an electrical connection, which is generally when there is a change in conductor cross-section. The short-circuit current value must be calculated at every stage of installation for different possible network configurations. This is done to determine the characteristics of the equipment that must withstand or switch the fault current. In order to choose the appropriate switching devices (circuit-breakers or fuses) and set the protection functions, four short-circuit values must be known: The root mean square value of the maximum short-circuit current (symmetrical three-phase short-circuit) This determines: – the breaking capacity of the circuit-breakers and fuses; – the temperature stress that the equipment must withstand. It corresponds to a short-circuit in the immediate vicinity of the downstream terminals of the switching device. It must be calculated to include a good safety margin (maximum value). The peak value of the maximum short-circuit current (value of the first peak of the transient period) This determines: – the making capacity of the circuit-breakers and switches; – the electrodynamic withstand of the trunkings and switchgear.
Short-circuits
83
A negligible impedance fault between A and B gives rise to a short-circuit current I sc limited by impedance Z sc : Z sc = R 2 +X 2 where X = Lω
In steady-state conditions, the short-circuit current is: I sc =
E Z sc
The real short-circuit current I sc is established according to a transient state having a non-periodic component and a higher amplitude than during the steady state. We shall consider two cases because the transient state differs according to whether the short-circuit is located on the power utility’s supply (in this case the generators are far enough apart for their effects to be ignored), or whether it is located at the terminals of a generator. 4.1.1. Establishment of the short-circuit at the utility’s supply terminals A voltage of e= E 2 sin(ωt +α ) is applied to a circuit comprising a resistor and reactor in series.
α represents a switching angle defining the voltage phase upon occurrence of the fault (the voltage sinusoidal phase the moment the fault occurs). If ϕ is the phase angle between the voltage and the current, then tgϕ = The current expression is shown to be (see Appendix A): I sc =
R ⎡ − ωt ⎤ E 2⎢ sin(ωt + α − ϕ )−sin(α − ϕ )e X ⎥ ⎥ Z sc ⎢ ⎦ ⎣
where:
Z sc = R2 + X 2 tgϕ =
X R
X . R
Short-circuits
85
Let us define the coefficient K which characterizes the ratio of the peak transient current to the steady-state r m.s. current: E Iˆ= K I a where I a = steady-state r m.s. current Z sc R ⎛ − π ⎜ K = 2 ⎜1+e X ⎜ ⎝
⎞ ⎟ ⎟ ⎟ ⎠
Note: the factor 2 comes from the fact that a peak current is being compared to a steady-state root mean square current. It is interesting to define K in relation to the ratio
R , which characterizes the X
network (see Table 4-1 and Figure 4-3). R is: X – between 0.05 and 0.3 for HV or MV;
Generally the ratio
– between 0.3 and 0.6 for LV (near transformers).
R X
K K 2 Table 4-1:
0
0.05
0.1
0.2
0.3
0.4
0.5
0.6
∞
2.83 2.62 2.45 2.17 1.97 1.82 1.71 1.63 1.41 2
1.85 1.73 1.53 1.39 1.29 1.21 1.15
1
K values, ratio between the peak transient current and the steady-state current, according to
R X
Short-circuits t (ms) R/X
10 (p = 0)
30 (p = 1)
50 (p = 2)
70 (p = 3)
∞
0.05
2.62
2.30
2.06
1.89
1.41
0.1
2.45
1.97
1.71
1.57
1.41
0.2
2.17
1.63
1.48
1.43
1.41
0.3
1.97
1.50
1.43
1.42
1.41
Table 4-2: development of
87
Iˆ R equal in relation to the time for ratios Ia X
to 0.05, 0.1, 0.2 and 0.3
Conclusion When a short-circuit occurs in an installation fed by a distribution network (far from the generators), a transient current occurs which lasts for several periods, i.e. between 20 and 80 ms. However, when circuit-breakers are not time-delayed, they generally have a lower tripping time than the duration of the aperiodic current and should therefore be able to break the aperiodic component (see section 8.2 for MV circuit-breakers and section 8.1 for LV circuit-breakers). For LV circuit-breakers, R (Table 8-2). the breaking capacity is defined in relation to cos ϕ = 2 X + R2
The peak value of the transient current is 1.6 to 2.5 times higher than the shortcircuit current value in steady-state conditions. It determines the electrodynamic forces that the trunkings and switchgear must withstand and the making capacity of the switching devices (see section 5.2). 4.1.2. Establishment of the short-circuit current at the terminals of a generator
It is assumed that the short-circuit is close enough to the generator for the cable impedance to be ignored compared with the generator impedance. Calculations on transient states of synchronous machines show that the current is expressed by: ⎡⎛ 1 1 i (t ) = E 2 ⎢⎜ " − ' ⎜ ⎣⎢⎝ X d X d
⎞ ⎛ 1 " E 2 1 ⎞ −t/Td' 1 ⎤ + ⎥ Cos (ω t + α ) − ⎟⎟ e −t/Td + ⎜⎜ ' − ⎟⎟ e X X X d" d ⎠ d ⎥ ⎠ ⎝ Xd ⎦
e − t/Ta
cos α
α represents a switching angle defining the voltage phase upon occurrence of the fault (the voltage sine curve phase at the moment the fault occurs). Current i ( t ) is maximum for α = 0.
88
Protection of Electrical Networks
Thus:
⎡⎛ 1 1 − i (t ) = E 2 ⎢⎜ " ⎜ ⎢⎣⎝ X d X d'
⎞ ⎛ 1 " E 2 −t/Ta 1 ⎞ − t/T ' 1 ⎤ ⎥ cos ωt − ⎟ e −t/Td + ⎜ ⎟e d + e ⎟ ⎜ X' ⎟ Xd ⎥ X d" ⎠ ⎝ d Xd ⎠ ⎦
E : single-phase r.m.s. voltage at the generator terminals Xd" : subtransient reactance Xd' : transient reactance Xd : synchronous reactance
Td" : subtransient time constant Td' : transient time constant Ta : aperiodic time constant The current is the sum of the aperiodic current: ic =−
E 2 − t/Ta e X d"
and of a damped sinusoidal current: ⎡⎛ 1 1 ia = E 2 ⎢⎜ − " ' ⎜ ⎣⎢⎝ X d X d
⎞ −t/T " ⎛ 1 1 − ⎟ e d +⎜ ⎟ ⎜ X' X d ⎠ ⎝ d
⎞ ' 1 ⎤ ⎥ cos ωt ⎟ e −t/Td + ⎟ Xd ⎥ ⎠ ⎦
The aperiodic component has a high value but a very short duration, from 10 to 60 ms (see Tables 4-3, 4-4 and 4-5 showing the aperiodic time constant values Ta ). For the damped sinusoidal component, the electrical variables evolve as if the machine reactance was variable and developed according to the three following periods: – subtransient ( Xd" ): lasting 10 to 20 ms after the start of the fault; – transient ( Xd' ): lasting up to 100 to 400 ms; – synchronous ( Xd ): synchronous reactance to be considered after the transient period. Let us note that in the order given, this reactance takes a higher value for each period:
Xd" < Xd' < Xd This leads to a gradual decrease in the short-circuit current. The short-circuit current is thus the sum of four components (see Figure 4-4).
90
Protection of Electrical Networks
It should be noted that the decrease in generator reactance is faster than that of the aperiodic component. This rare case may raise switching difficulties for the circuit-breakers and saturation problems for the magnetic circuits as the current does not reach zero until after several periods. Standard electrical characteristics of generators
The values Xd" , X d' and Xd are expressed as percentages (see section 4.2.1.3). S (kVA)
75
200
400
800
1,600
2,500
Xd" (%)
10.5
10.4
12.9
10.5
18.8
19.1
Xd' (%)
21
15.6
19.4
18
33.8
30.2
Xd (%)
280
291
358
280
404
292
Ta (ms)
9
15
22
28
47
65
Td" (ms)
6
10
14
18
22
23
Td' (ms)
80
30
140
160
235
320
Table 4-3: electrical characteristics of Leroy-Somer 75 to 2,500 kVA three-phase, four-pole generators with a phase-to-phase voltage of 400 V and frequency of 50 Hz
S (kVA)
2,200
2,800
3,500
Xd" (%)
15.5
14
13
Xd' (%)
25.5
24.5
23
X d (%)
235
230
225
Ta (ms)
50
54
57
Td" (ms)
22
24
26
Td' (ms)
240
260
280
Table 4-4: electrical characteristics of Leroy-Somer 2,200, 2,800 and 3,500 kVA threephase, four-pole generators with a phase-to-phase voltage of 6 kV and frequency of 50 Hz
Short-circuits
S (kVA)
1,500
2,500
3,250
X d" (%)
15.5
14.5
14
Xd' (%)
27.5
26.5
25.5
Xd (%)
255
255
250
Ta (ms)
37
46
52
Td" (ms)
21
24
26
Td' (ms)
230
260
280
91
Table 4-5: electrical characteristics of Leroy-Somer 1,500, 2,500 and 3,250 kVA three-phase, four-pole generators with a phase-to-phase voltage of 11 kV and frequency of 50 Hz
Development of short-circuit current peak values,
Iˆ
in relation to the time
2In
(see Table 4-6)
I n is the nominal current of the generator.
⎛ 1⎞ The peak values occur at times t =⎜ p+ ⎟T ⎝ 2⎠ 2π where p is an integer and T = is voltage period (T = 20 ms for f = 50 Hz), thus:
ω
⎡⎛ 100 100 ⎞ ⎟e − t / Td" = ⎢⎜ − " ' 2 I n ⎢⎣⎜⎝ X d X d ⎟⎠
⎤ ⎛ 100 100 ⎞ ⎟ e − t / Td' + 100 ⎥ + 100 e−t / Ta +⎜ − ' ⎜X ⎟ X d ⎥ X d" ⎝ d Xd ⎠ ⎦
Iˆ
where the values X d" , X d' and X d are expressed as percentages (see section 4.2.1.3). 10
30
50
90
150
310
610
∞
75
8.3
3.8
2.8
1.8
1
0.45
0.36
0.36
200
10.81
4.04
1.86
0.67
0.39
0.344
0.344
0.344
400
11
6.5
4.6
3
2
0.81
0.34
0.28
800
14.2
8.7
6
3.7
2.4
1.1
0.47
0.36
t(ms) S (kVA)
Table 4-6: development of
Iˆ
in relation to the time for the 75, 200, 400 and 800 kVA
2In generators defined in Table 4-3
92
Protection of Electrical Networks
Holding the short-circuit current at approximately 3 I n for several seconds
When the subtransient and transient periods are over, i.e. after a time of 0.5 to 1 second, the short-circuit current is lower than the nominal current, i.e. from 0.3 to 0.5 In (see Table 4-6). The values given above are design values. In practice, manufacturers like Leroy-Somer have methods for holding the shortcircuit current at approximately 3 In for several seconds to allow the protective devices to operate when they are time-delayed, for selectivity reasons, for a time greater than Td' ≈ 100 ms. The holding value 3 In is close to the current value during the transient period where: E where Xd' ≈ 30% I sc ≈ ' Xd
I sc is thus close to 3 In . When the current is not held at 3 In , protection against short-circuits may be provided by voltage restrained overcurrent protection (see section 7.24). Note: the method generally used to hold the short-circuit current at 3 In is compound excitation, i.e. series-parallel excitation. The parallel voltage drops when a short-circuit occurs, leading to a drop in parallel excitation; the short-circuit current, however, is higher than the nominal current and the series excitation increases. Combined, the two phenomena lead to a short-circuit current held at 3 In for several seconds. 4.2. Short-circuit current calculating method
The short-circuit current calculating method presented in this document is the impedance method. It is applied to calculations by hand and produces sufficiently accurate results for most applications. It helps with the understanding of more accurate methods, such as IEC 60909, which are generally applied using computer software programs. The aim of this section is to give all the elements needed to calculate the following short-circuits: – symmetrical three-phase fault;
94
Protection of Electrical Networks 2 2 Z sc= (ΣR ) +(ΣX )
ΣR : sum of series resistances through which the fault current flows ΣX : sum of series reactances through which the fault current flows In practice, the equivalent supply source impedance is calculated first (power supply provided by the utility or generator), then the impedances of each transformer, cable or line through which the fault flows. Each impedance must be recalculated for the voltage level of the presumed fault (see section 4.2.1.1). Note: in medium and high voltage, standard IEC 60909 (Table 1) applies a coefficient of 1.1 to the nominal voltage in order to calculate the maximum shortcircuit current, thereby giving: I sc3 =
1.1U n
(in MV and HV)
3 Z sc
4.2.1.1. Equivalent impedance of an element across a transformer For example, for a low voltage fault, the contribution of a cable upstream of the MV/LV transformer will be: ⎛ U LV R LV = R HV ⎜⎜ ⎝ U HV
⎞ ⎟⎟ ⎠
2
and ⎛ U LV X LV = X HV ⎜⎜ ⎝ U HV
⎞ ⎟⎟ ⎠
2
thus: ⎛ U LV Z LV = Z HV ⎜⎜ ⎝ U HV
⎞ ⎟⎟ ⎠
2
This formula can be applied whatever the cable voltage level, i.e. even across several transformers in series.
Short-circuits
97
hence:
U sc (%) Vn 100 I n
Z=
Vn : single-phase nominal voltage Transformer manufacturers give the apparent nominal power Sn in kVA:
Sn = 3 Vn I n Z=
U sc (%) 3Vn2 100 Sn
Z=
U sc (%) U n2 100 Sn
Un : phase-to-phase nominal voltage = 3 Vn Note: for transformers fitted with tap changers, the voltage U n is that obtained for the main position of the changer (see IEC 60909, section 8.3.2.2). Rotating machines '
"
Instead of giving the characteristic impedance values ( X d , Xd , X d ) of motors and generators in ohms, manufacturers give them as a percentage ( Xd (%),
X d' (%), X d" (%)). By definition, the following relation applies:
X (Ω) =
X (%) 100
Vn In
Manufacturers of rotating machines give the apparent nominal power Sn in kVA:
Sn = 3 Vn I n 3Vn2 X (%) X (Ω) = Sn 100 X (Ω) =
U n2 X (%) Sn 100
98
Protection of Electrical Networks
Un : nominal phase-to-phase voltage Thus:
X d (Ω) =
U n2 X d (%) Sn 100
X d' ( Ω ) =
U n2 X d' (%) Sn 100
X d" ( Ω ) =
U n2 X d" (%) Sn 100
4.2.1.4. Impedance values of different network elements Upstream network impedance
Knowledge of the upstream network is generally limited to the indications supplied by the utility, i.e., the short-circuit power S sc (in MVA) only:
Za =
U n2 S sc
U n : network nominal phase-to-phase voltage The upstream network is generally considered to be a pure reactance, i.e.
Za ≅ Xa .
We saw in section 4.1.1 that the ratio
Ra is between 0.05 and 0.3 for MV. Xa
Let us take, for example Ra = 0.3, thus: Xa
(
)
Za2 = Ra2 + X a2 = ( 0.3) + 1 X a2 = 109 . X a2 2
hence:
X a = 0.96 Za As a first approximation, we shall thus take Za = X a . Note: the approximation Za = X a is better the lower the ratio
Ra is. Xa
Short-circuits
99
Generator power supply impedance
In section 4.1.2, we saw that the short-circuit current developed in the following three periods: " i) subtransient ( Xd ): lasting 10 to 20 ms after the start of the fault; ' ii) transient ( X d ): lasting up to 100 to 400 ms; iii) synchronous ( X d ): synchronous reactance to be considered after the transient period; – To check electrodynamic stress, the maximum short-circuit current is calculated on the basis of the subtransient reactance:
I sc 3 =
Un 3 X d"
U n : nominal phase-to-phase voltage – To check heat stress in equipment, the maximum short-circuit current is calculated on the basis of the transient reactance:
I sc 3 =
Un 3 X d'
– To set the threshold of phase overcurrent protective devices, notably when the generator is able to operate cut-off from the utility network, the minimum shortcircuit current (see section 4.4.2) is calculated on the basis of the transient reactance and the negative sequence reactance X ( 2) (see section 4.2.2.1).
I sc 2 ,min =
Un X + X (2) ' d
The steady state is not generally taken into account, assuming that the protective devices switch the current during the transient state or that the short-circuit current is held at 3 In (see section 4.1.2). The protection threshold is therefore set below this value. If this is not the case, restrained voltage overcurrent protection is used (see section 7.24): – To determine the breaking capacity of low voltage circuit-breakers, the maximum short-circuit current is calculated on the basis of the subtransient Un reactance I sc 3 = . It is generally lower than the short-circuit current supplied 3 X d" by the utility. – To determine the breaking capacity of high voltage circuit-breakers, the periodic component value and the aperiodic component value must be calculated
100
Protection of Electrical Networks
during the minimum opening time of the circuit-breaker, to which is added a half period of the rated frequency. These values must be passed on to the manufacturer for approval or tests (see section 8.2). Standard generator subtransient, transient, synchronous and negative-sequence impedance values (Tables 4-7, 4-8 and 4-9) S (kVA) Xd" (%) Xd' (%)
X d (%) X ( 2)
(%)
75
200
400
800
1,600
2,500
10.5
10.4
12.9
10.5
18.8
19.1
21
15.6
19.4
18
33.8
30.2
280
291
358
280
404
292
13.1
11.3
15.1
11.7
22.2
21.2
Table 4-7: subtransient, transient, synchronous and negative-sequence impedances of LeroySomer four-pole generators with a phase-to-phase voltage of 400 V and frequency of 50 Hz
S (kVA) Xd" (%) Xd' (%)
2,200
2,800
3,500
15.5
14
13
25.5
24.5
23
X d (%) X ( 2)
235
230
225
17
15.5
14.5
(%)
Table 4-8: subtransient, transient, synchronous and negative-sequence impedances of LeroySomer four-pole generators with a phase-to-phase voltage of 6 kV and frequency of 50 Hz
S (kVA) Xd" (%) Xd' (%)
1,500
2,500
3,250
15.5
14.5
14
27.5
26.5
25.5
X d (%) X ( 2)
255
255
250
17.5
16.5
16
(%)
Table 4-9: subtransient, transient, synchronous and negative-sequence impedances of LeroySomer four-pole generators with a phase-to-phase voltage of 11 kV and frequency of 50 Hz
Short-circuits
101
Note: the resistance of the windings is negligible compared with the reactance R 0.2 I so
314
Protection of Electrical Networks
thus: I psc > 0.24 I n
This condition is met as long as the synchronous impedance Xd is lower than 415%, which is generally the case (see Tables 4-3, 4-4 and 4-5). The time delay, fixed by the selectivity system, can be longer than the duration of the transient period. Note: restrained voltage overcurrent protection is also referred to as minimum impedance protection. Indeed, according to Figure 7-64, we can see that the protection is activated for a constant ratio U , i.e. a threshold impedance Zset. I Physically, it can be said that the protection measures the impedance downstream and, when this is lower than the threshold Zset, the protection is activated. The low value of the downstream impedance is characteristic of a short-circuit or a high overload. 7.25. Protection by gas, pressure and temperature detection (DGPT)
The DGPT (detection of gas, pressure and temperature) is a protective device used for liquid-insulated transformers. It detects anomalies inside the liquid dielectric such as emission of gas, or a rise in pressure or temperature, and causes the transformer switching device (circuitbreaker or switch-fuse) to trip. The relay units corresponding to these functions are mainly designed to protect “totally filled”, sealed and immersed transformers. This protection can carry out the following four functions. Detection of gaseous emission
In a liquid-insulated transformer, an internal fault always causes a fairly large gaseous emission due to the decomposition of the insulating materials (liquids or solids) under the action of the electric arc. Detection of a sealing anomaly indicated by a drop in the dielectric level
There are two levels of detection: – a visual indication of a drop in the level via a first red floater;
Protection Functions and their Applications
315
– electrical message to the switching device operating mechanism via a second floater when there is a large drop in the level. Note: the transformer can be easily refilled via the upper part of the relay unit. Detection of excessive pressure in the transformer tank using an electrical contact pressure switch
This pressure switch is pre-set in the factory by the transformer manufacturer to between 0 and 500 millibars (normal value: 200 millibars). When an internal fault due to a high short-circuit current occurs, the gaseous emission causes the pressure switch to be activated in several tenths of a second. Detection of an abnormal temperature in the dielectric
This detection is both visual (thermometer with 0 to 120°C graduations) and electrical (1 or 2 thermostats). These thermostats (liquid expansion-based) are independent and can be set to between 30 and 120°C (increments of 5°C), with one giving the alarm (normal setting: 95°C), and the other causing the switching device to trip (normal setting: 100°C). The sensitive part of the thermometer is located in the same pocket tube as that of the thermostat probes. Note: a Buchholz relay provides protection for a breathing transformer. For a fault that is not very serious, the gaseous emission is collected in an upper part of the relay and an alarm is activated when too much gas accumulates. For a serious fault, the large quantities of gas produced forcefully drives back part of the oil in the tank towards the conservator. A floater driven by the oil flux gives the order for the transformer to be put out of service. This principle leads to an operating time of several tenths of a second for a serious fault. 7.26. Neutral to neutral unbalance protection (ANSI code 50 N or 51 N)
This protection is designed to protect double star-connected capacitor banks (see Figure 7-65). The deterioration of the capacitor elements leads to an unbalance that causes a current to circulate between the two neutral points (see section 10.6.3). This current is detected by the protection, which causes the switching device to trip.
Chapter 8
Overcurrent Switching Devices
Overcurrents in an electrical network may be caused by a short-circuit or an overload. The switching devices used to clear these overcurrents are circuit-breakers and fuses. In this chapter we will define the electrical specifications of fuses and circuitbreakers. Since low and medium voltage specifications are different, they will be dealt with in separate sections. Definition Prospective short-circuit current: this is the short-circuit current in steady-state operating conditions that would occur if the impedance of the switching device was zero.
8.1. Low voltage circuit-breakers Rated (1) operating voltage Ue This is, or these are, the voltage(s) at which the device can be used. Rated (1) current In This is the maximum value of the current that a circuit-breaker, fitted with a tripping relay, can withstand at an ambient temperature specified by the manufacturer and in compliance with the specified heating limits.
Overcurrent Switching Devices
319
Short-circuit relay trip-current setting ( Im ) Short-circuit tripping relays (magnetic or slightly time delayed) are designed to cause high-speed opening of the circuit-breaker upon occurrence of high overcurrents. Their operating threshold Im is either fixed by standards (e.g. IEC 60898 for domestic circuit-breakers, or stipulated by the manufacturer for industrial circuitbreakers governed by IEC 60947-2): – for the latter circuit-breakers, there is a wide variety of tripping relays allowing the user to adapt the protective functions of the device to the requirements of the circuit to be protected, even in the most specific cases; – for circuit-breakers with adjustable thresholds, setting is not continuous but carried out in steps. This must be taken into account when studying the selectivity. Table 8-1 gives the average circuit-breaker operating thresholds for overloads and short-circuits. Figures 8-2 and 8-3 give the standard operating curves for a thermal-magnetic circuit-breaker and an electronic circuit-breaker. Some tripping relays have an I 2 × t = constant curve as an option. type of trip-relay
overload protection
short-circuit protection
IEC 60898 domestic circuitbreakers
thermalmagnetic
I r =I n
low setting type B 3In≤Im